Blowers Performance Curve
While multi-rating tables are convenient, fan performance curves offer additional information such as - how much reserve pressure head exists between the design pressure and the peak static pressure, the maximum power the fan might draw, and the efficiency of operation.
Fan curves are based on laboratory test data and are sometimes referred to as "test curves". A typical test curve will often define the performance parameters for a specific design and size of fan, operating at a given speed, moving a gas of a given density. Inspection of this graph will show that it is actually composed of four separate curves:
• Static Pressure vs. Volume Curve: This plot is the one often referred to as the "fan curve" or "characteristic curve" because it defines all the possible pressure-volume combinations the fan is capable of producing given stated conditions (i.e. rpm and gas density). Note that this curve has two regions - one marked by dashed lines and the other by a solid line. Fans must be selected so that the design point is located on a solid portion of the curve, preferably in an area of high operating efficiency. ...
... Operation on the dashed portion of the curve should be avoided as it is a zone of potentially unstable performance. For this reason it is wise to allow some reserve between the peak static pressure and the design pressure to compensate for a higher resistance to flow than anticipated by the design calculation.
• Static Efficiency vs. Volume Curve: In most instances it is desirable to have a fan perform as close to its peak efficiency as possible. The static efficiency vs. volume curve illustrates the efficiency of fan performance at a glance.
• Power vs. Volume Curve: This plot illustrates the power draw of the fan for any point on the characteristic curve.
• System Curve: The system curve defines the volume flow rate versus pressure characteristics of the system in which a fan will be installed.
For most applications, the volume flow rate to pressure relationship is governed by the following equation, often called the "duct law":
Once the system designer has determined the system pressure loss (P) for one flow rate (CFM), it is very easy to calculate the corresponding pressure loss for any other flow rate using this "law". The system curve is not included on the performance curve when it is issued from the fan manufacturer and its determination is left to the system designer.
For additional information please refer to http://www.northernindustrialsupplycompany.com/burlington/request5.html
Oleg Tchetchel
Industrial Ventilating Designer
airknife@cogeco.ca
Northern Fan Co.
http://www.northernindustrialsupplycompany.com/burlington/request7.html
http://www.northernindustrialsupplycompany.com/burlington/request2.html
Add Comment
Others Articles
1. Boost Your Farm Efficiency With Vishal 328 LealAuthor: Ajay tiwari
2. Effortless Office And Budget Relocations In Auckland
Author: Accurate Movers
3. Stainless Steel Shower Tray Auckland: Strong, Sleek Solutions
Author: Kiwi Stainless
4. Best Cash For Cars In Auckland
Author: Cars 4 Cash
5. Trusted Junk Car Buyers In Auckland
Author: Cars 4 Cash
6. Cryptocurrency In Medical Billing: A Revolutionary Approach
Author: Albert brown
7. Stainless Steel Auckland Kitchen Makeover
Author: Kiwi Stainless
8. The Long-term Effects Of Childhood Trauma And How To Heal
Author: ImPerfect
9. Top It Companies In India: Driving Global Innovation
Author: Johnny
10. Uk Health And Wellness: Trends, Challenges, And Opportunities
Author: Alex
11. Trending Job Categories On Aamdhane
Author: Aamdhane
12. Enhance Your Hearing Experience With Custom Made Ear Plugs And Hearing Aid Solutions In Cardiff
Author: Steve Jones
13. Industrial Hose Pipe Couplings - Manxpower
Author: MANXPOWER
14. Best Astrologer In Koppal
Author: Astrology56
15. Unveiling Photo Editing Tricks: What You Need To Know
Author: Sam