Why Dc 4~20ma Is Chosen For Signal Transmission Of Transmitters?

Profile Picture
By Author: Jane Yu
Total Articles: 29
Comment this article
Facebook ShareTwitter ShareGoogle+ ShareTwitter Share

In industry, it is necessary to measure all kinds of electric and non electric parameters, such as current, power, temperature, pressure, speed and angle, etc.

In industry, 4 ~ 20mA current signal is widely used to transmit these analog quantities, so that the field data can be transmitted to the screen of control room or display equipment hundreds of meters away.


So why does the transmitter choose DC4 ~ 20mA as the transmission signal?

1. Safety of Field Applications
The key point of safety is explosion-proof. The spark energy caused by the upper limit of 20mA current is not enough to ignite gas. At the same time, the selection of 20mA current also reduces the static and dynamic power consumption to the minimum.

And the power supply voltage of the transmitter that outputs 4 ~ 20mA DC standard signal is usually 24V DC.

The primary reason for using DC voltage is that it can avoid using capacitance and inductance with large capacity, and users only need to consider the distributed capacitance and inductance of the connecting wire between the transmitter and the instrument in the ...
... control room.

For example, the distribution capacitance of 2mm conductor is about 0.05 μ F/km. The inductance of single wire is about 0.4mh/km. They are much lower than the value of detonating hydrogen, which is very beneficial for explosion-proof.


2. Current Source is Better than Voltage Source
When the distance between the field and the control room is far, and the resistance of the connecting wire is large, if you choose to use the voltage source signal for remote transmission, there will be a large error due to the partial voltage between the wire resistance and the input resistance of the receiving instrument.

If you choose the current source signal for remote transmission, as long as there is no branch in the transmission circuit, the current in the circuit will not change with the length of the wire, so that the accuracy of transmission can be ensured.

In addition, the amplitude of noise voltage in industrial field may reach several volts, but the noise power is very small, so the noise current is usually at nA level, and the error caused by 4-20mA transmission is very small.

the internal resistance of current source tends to be infinite, and the wire resistance series does not affect the accuracy in the circuit, so the signal can be transmitted hundreds of meters on the common twisted pair.

Because of the high internal resistance and constant current output of current source, only a 250 ohms resistance is needed to obtain the sampling voltage of 5V at the receiver. Meanwhile, the voltage noise of class nA is very weak for the receiver with low input impedance.


3. Reason of Choosing 20mA as the Maximum Current of Signal
The maximum current selection of 20mA is based on the consideration of safety, practicality, power consumption and cost.

Only low voltage and low current can be used for safety spark instruments, and 4 ~ 20 mA current and 24 V DC are safe even for flammable hydrogen. When the voltage is 24V DC, the ignition current of hydrogen need to be 200 mA, which is much higher than 20 mA.

In addition, you need to consider the connection distance, load, power consumption and cost too when selecting 20mA. And there are also certain requirements for the electronic components and power supply.


4. Reason of Choosing 4mA as Starting Current of Signal
Most transmitters with output of 4 ~ 20mA are two-wire. Two wire system means that the power supply and load are connected in series with a common point. Only two wires are used for signal communication and power supply between field transmitter and instrument in control room.

Some people may have the question, why is the starting signal not set as 0mA?

Here are two reasons:

Some transmitter circuits cannot work without static working current.

The starting current of the signal is 4mA DC, which does not coincide with the mechanical zero point. This "live zero point" is helpful to identify the faults such as power failure and disconnection.

More About the Author

OKmarts.com Online Store | We provide leading brands of refrigeration compressors, servo motors, Air cylinder and more all over the world. More product's information please visit https://okmarts.com/

Total Views: 210Word Count: 664See All articles From Author

Add Comment

Computers Articles

1. Expert Ppc Services In Pune
Author: Brandrisic Media

2. The Future Of Online Medicine Delivery Apps In 2025
Author: simonharris

3. Where Can I Book A Doorstep Laptop Repair Service?
Author: Smita Join

4. Unlocking Business Potential With It Services And Lexington Managed Services
Author: naviworld1h

5. Top 5 Workflow Automation Software Of 2025
Author: Ben Gross

6. Ensuring Medication Safety With Tempgenius: Medication Temperature Monitor And Remote Temperature Probe
Author: Chris Miller

7. Spiral Model Sdlc: Top Choice For Large, High-risk Software Projects?
Author: goodcoders

8. How To Develop An Employee Scheduling App Like Hotschedules?
Author: goodcoders

9. How To Build A User-friendly Mobile Website? 10 Super Tips From Experts
Author: goodcoders

10. How To Choose The Right Refurbished Desktop For Your Needs: A Buyer’s Guide
Author: Scogo Store

11. Why Choose Refurbished Laptops Over New Ones In 2025?
Author: Scogo Store

12. Cloud Computing Trends 2025
Author: Ben Gross

13. Gst-billing-software
Author: Priyanka Patil

14. Digital Transformation In Higher Ed: Leveraging Crm For Student Recruitment
Author: E2S Team

15. How To Contact Sbcglobal Email Support: A Step-by-step Guide
Author: SBCGlobalInfo

Login To Account
Login Email:
Password:
Forgot Password?
New User?
Sign Up Newsletter
Email Address: